Change the cooling water entirely to prevent algae and mineral buildup.

If your chiller starts beeping, check the display for these standard codes found in the : E1 Ultrahigh room temperature Improve ventilation or lower room temp. E2 Ultrahigh water temperature Check for clogged dust gauze or pump failure. E3 Ultralow water temperature Normal in winter; use a heater if necessary. E4 Room temp sensor failure Inspect sensor wiring or replace sensor. E5 Water temp sensor failure Check the probe connection. E6 Water flow alarm Check for kinked hoses or low water levels. 🧹 Maintenance Schedule

Use purified or distilled water. Fill until the water level reaches the green area of the gauge.

The S&A Teyu CWFL-6000 is engineered to handle the intense heat of industrial fiber lasers. It features two independent cooling channels: Cools the laser optics and cutting head. Low-Temp Channel: Cools the fiber laser source. Technical Snapshot: